Input Voltage
|
180 to 260V AC/1 Ph/50±2Hz
|
|
Output Voltage
|
220VAC/230VAC±1%
|
|
Frequency Effect
|
Approx. 1.5% change in output voltage, for 1% change
in input frequency
|
|
Efficiency
|
90%, Typical, at full load
|
|
Common-Mode-Noise Attenuation*
|
1:3000, Typical (10Khz to 5 MHz; 85 to 21 db, typ.)
|
|
Normal-Mode-Noise Attenuation*
|
1:2500, Typical (10Khz to 5 MHz; 62 to 21 db, typ.)
|
|
Output waveform
|
Sinusoidal
|
|
Total Harmonic Distortion
|
5% (Typical) at 230VAC-Input & full-load change
|
|
Output Voltage Correction
|
2 cycle (max.) for no load to full load conditions
|
|
Operating Temperature
|
-5ºC to +50ºC
|
|
Operating Humidity
|
95% RH , non condensing
|
|
Ratings (VA)
|
50, 100, 150, 250, 350, 400, 500, 750, 1000, 1500,
2000, 3000 & 5000
|
|
Metering
|
0-300v, M.I. meter; Accuracy ± 2% FSD
(To monitor output voltage)
|
|
Environment
|
0-40°C, 95% RH (non condensing)
|
|
Caution :
Keep CVT away from magnetic storage devices and displays,
like floppy disks, magnetic tapes, monitors etc. Do
not use with highly inductive type of loads or with
loads requiring heavy starting current surges like motors.
Do not use CVTs with generators whose frequency variations
are outside the specified range.
|
|
*With output Floating
CVT with special input range available on request
|