In today's scenario, the utility power available has,
unfortunately, several unwanted parameters like sags, surges, voltage variation,
frequency variation, brownouts, spikes, dips, blackouts,etc.
However, with more and more sensitive and demanding equipment being deployed by
the day, the need for clean power has become all the more essential in order to
ensure its correct functioning and to afford total protection.
Elnova On-Line Ups Systems offer clean power and total protection to your costly equipment.
These state-of-the art Double Conversion type UPS Systems employing High
Frequency PWM Technique using MOSFET/IGBT as the Main Switching Device for
inverters are technically superior UPS system giving Pure Sine Wave Output.
Compact and well engineered, Elnova On-Line UPS have been tried and tested in virtually
all applications, and have been found to be extremely reliable and consistent in delivering
optimum performance. These systems, besides being easy to install and operate, are simple to
maintain, should the need ever arise.
This range of UPS Systems is brought to you by Elnova. Promoted by technocrats having wide
experience in the field, Elnova today is an established company with country-wide sales and
service network and a product range that commands an enviable record of high MTBF and low MTTR.
|
| |
| SALIENT FEATURES |
- VHD Logic employed for the first time in India.
- True On-Line Double Conversion type UPS System
- High Frequency PWM Design Using IGBT/MOSFET
- Instantaneous sine wave reference technique for superior over all performance.
- Compact and well engineered architecture.
- Wede input voltage tolerance range suitable for all types and capacities of batteries
- Pure sine wave output
- Smooth and silent operation
- Complete annunciation on the front panel
- Excellent dynamic response for step load change
- Short circuit/overload protected
- Fast correction rate for line and load regulation
- High inrush/peak current handling capacity
- Easy to install, use and maintain
- Superior performance to price analysis
|
| TECHNICAL INFORMATION
/ SPECIFICATIONS |
|
Input Conditions and Specifications
|
|
Input Voltage
|
Single Phase 160-270VAC, 2 Wire + E Threee Phase 400V(330-470VAC), 4Wire + E
|
|
Frequency
|
50Hz ± 6% (47 - 53 Hz)
|
|
Input / Cutoff
|
Automatic for Input Under Voltage & Input Over
Voltage
|
|
DC Voltage
|
Single Phase (180VDC) for 5,6,7.5 & 10KVA
Three Phase (360VDC) for 5 to 120KVA
|
|
Output Conditions and Specifications
|
|
Output Voltage
|
Single Phase 220/230VAC ± 1%, 2 Wire +E
Three Phase 400/415VAC ± 1%, 4 Wire +E
|
|
Output Frequency
|
50Hz ± 0.2%
|
|
Load Power Factor
|
Unity to 0.6 lag
|
|
Waveform
|
Sine Wave
|
|
Distortion
|
<2% on Linear Load and non-linear load
|
|
Inverter Efficiency
|
90% (Typical)
|
|
Transient Voltage
|
< ± 5% for 100% Step Load Change (corrected within 50 ms.)
|
|
Crest Factor
|
3 : 1
|
|
Over Load
|
120% for 10 mis. 150% for 10 sec.
|
|
Noise
|
< 55 db at a distance of one metre
|
|
Environment
|
0 - 50°C, 95% RH Max (non condensing)
|
|
Cooling
|
Forced air type
|
|
|
|