In today's scenario, the utility power available has, unfortunately, several unwanted parameters like sags, surges, voltage variation, frequency variation, brownouts, spikes, dips, blackouts,etc.

However, with more and more sensitive and demanding equipment being deployed by the day, the need for clean power has become all the more essential in order to ensure its correct functioning and to afford total protection.

Elnova On-Line Ups Systems offer clean power and total protection to your costly equipment.

These state-of-the art Double Conversion type UPS Systems employing High Frequency PWM Technique using MOSFET/IGBT as the Main Switching Device for inverters are technically superior UPS system giving Pure Sine Wave Output.

Compact and well engineered, Elnova On-Line UPS have been tried and tested in virtually all applications, and have been found to be extremely reliable and consistent in delivering optimum performance. These systems, besides being easy to install and operate, are simple to maintain, should the need ever arise.

This range of UPS Systems is brought to you by Elnova. Promoted by technocrats having wide experience in the field, Elnova today is an established company with country-wide sales and service network and a product range that commands an enviable record of high MTBF and low MTTR.

 
SALIENT FEATURES
  • VHD Logic employed for the first time in India.
  • True On-Line Double Conversion type UPS System
  • High Frequency PWM Design Using IGBT/MOSFET
  • Instantaneous sine wave reference technique for superior over all performance.
  • Compact and well engineered architecture.
  • Wede input voltage tolerance range suitable for all types and capacities of batteries
  • Pure sine wave output
  • Smooth and silent operation
  • Complete annunciation on the front panel
  • Excellent dynamic response for step load change
  • Short circuit/overload protected
  • Fast correction rate for line and load regulation
  • High inrush/peak current handling capacity
  • Easy to install, use and maintain
  • Superior performance to price analysis
   TECHNICAL INFORMATION / SPECIFICATIONS

Input Conditions and Specifications

Input Voltage

Single Phase 160-270VAC, 2 Wire + E Threee Phase 400V(330-470VAC), 4Wire + E

Frequency

50Hz ± 6% (47 - 53 Hz)

Input / Cutoff

Automatic for Input Under Voltage & Input Over Voltage

DC Voltage

Single Phase (180VDC) for 5,6,7.5 & 10KVA
Three Phase (360VDC) for 5 to 120KVA

Output Conditions and Specifications

Output Voltage

Single Phase 220/230VAC ± 1%, 2 Wire +E
Three Phase 400/415VAC ± 1%, 4 Wire +E

Output Frequency

50Hz ± 0.2%

Load Power Factor

Unity to 0.6 lag

Waveform

Sine Wave

Distortion

<2% on Linear Load and non-linear load

Inverter Efficiency

90% (Typical)

Transient Voltage

< ± 5% for 100% Step Load Change (corrected within 50 ms.)

Crest Factor

3 : 1

Over Load

120% for 10 mis. 150% for 10 sec.

Noise

< 55 db at a distance of one metre

Environment

0 - 50°C, 95% RH Max (non condensing)

Cooling