Elnova Limited : UPS Manufacturer, UPS Distributor, UPS Supplier, Constant Voltage Transformer, CVT Manufacturer, CVT Supplier, CVT Distributor, DC Power Supply, Power Supply System, Power Supply System Manufacturer, Battery, Battery Manufacturer, Battery Distributor, Indian Battery Manufacturer, SMF Battery, Electronic Components, Electronic Components Manufacturer, Indian Electronic Component Supplier/Distributor, ISO Certified Company sealed maintenance free batteries, smf batteries manufacturer, indian smf battery supplier, battery manufacturer, smf battery distributor, smf battery exporter, komatsoo batteries
PRODUCTS
  UPS  |  CVT  |  DC Power Supply  |  SMF Battery  |

   

SMF Battery
    Sealed Maintenance Free Battery


  Technical Information / Specification

Battery Type

Nominal Voltage (V)

Nominal Capacity 20 Hr. AH

L

Dimensions in mm
W

H

Height with Terminal

Weight Approx. In Kgs,

Assembly Figure

Terminal
Position     Type

K-12-7.5

 

7.5

151

65

94

102

2.635

5

F1

K-12-12

 

12

151

99

95

100

4.270

5

F1

K-12-18

 

18

181

76

167

167

6.283

25

F3

K-12-28

12

28

166

175

125

125

9.794

25

F3

K-12-45

 

45

198

166

171

171

14.109

25

F4

K-12-65

 

65

350

166

174

174

23.550

25

F4

K-12-100

 

100

406

172

210

244

37.510

20

F5



  Terminal Type & Terminal Position
Terminal Type & Terminal Position


Terminal Type & Terminal Position


  Battery Characteristics Charts

Discharge current and final discharge voltage

Discharge Current (A)

Final Discharge Voltage (V/cell)

0.2C (A)

1.75

0.2C (A) < 0.5C

1.70

0.2C (A) < 1.0C

1.55

(A) 1.0C

1.30


Battery Characteristics Charts

Battery Characteristics Charts
Battery Characteristics Charts

Battery Characteristics Charts

Battery Characteristics Charts


  Charge Method


Dependable performance and long service life of Komatsoo batteries depend on correct charging. Faulty procedures or inadequate charging equipment result in decreased battery life and/or unsatisfactory performance. Any of the conventional charging techniques may be used, but to obtain maximum service life and capacity, along with acceptable recharge time, constant current and voltage charging is recommended.

A charge quantity of 110-120% of the previous discharge quantity is needed to fully charge the battery. The charging voltage of battery decreases with increasing temperature and increases with decreasing temperature. At temperature below 5°C, the temperature compensation for charge voltage is necessary.

Overcharging should be avoided. As a result of too high a charge voltage, excessive current will flow after reaching full charge causing decomposition of water in the electrolyte and hence, premature aging and loss of AH capacity, Undercharging should also be avoided. If too low a charge voltage is applied, the charger current output will essentially stop before the battery is fully charged, This allows some of the lead sulphate to remain on the plates, which will eventually reduce AH capacity. The inital current limit must be within 0.1C to 0.3C.

Application

Standby Use

Cycle Use

Charge method

Constant Voltage

Setting voltage (v/cell)

2.25-2.30

2.40-2.50

Temperature factor

-3.3mV/°C/Cell

-5.0mV/°C/cell

Max. Charge current (CA)

0.3

0.3

Charge

Discharge 100%

Time, 20°C

Discharge 50%

24 h
20h

16 h
10 h

Temperature

0 to 40 °C



Recommended Recharging Interval & Method

Storage Temperature

Recharge Interval & Method

below 20°C (68°F)

6 months, charge for 16-24 hrs. at 2.3V/cell

21°C - 30°C (69.8°F - 86°F)

3 months, charge for 5-8 hrs. at 2.4V/cell

above 30°C (86°F), but suggest avoid storing at

1 month, charge for 5-8 hrs. at 0.05 CA

temperatures above 30°C

 


Handling Instructions

  • Don't short the terminals
  • Don't place the battery near or in fire
  • Don't use the battery in a container or bag without proper ventilation.
  • Operate at a temperature between 15°C to 50°C. But use at cyclic service, 5°C to 35°C range is recommended.
  • To properly store the battery, remove from equipment or charger and store in a dry and cool place.
  • Immediately recharge after discharging.
  • If sulphuric acid from the battery is spilled on skin or clothing, wash immediately with water. If acid comes in contact with eyes, wash with large amounts of water and immediately see a doctor.
  • To obtain maximum life, the R.M.S. ripple current should be regulated to less than 0.1C(A)
  • Avoid mixed use of batteries. Different capacities, manufacturing lots, or manufacturers may cause damage to the battery or other equipment.