Elnova Limited : UPS Manufacturer, UPS Distributor, UPS Supplier, Constant Voltage Transformer, CVT Manufacturer, CVT Supplier, CVT Distributor, DC Power Supply, Power Supply System, Power Supply System Manufacturer, Battery, Battery Manufacturer, Battery Distributor, Indian Battery Manufacturer, SMF Battery, Electronic Components, Electronic Components Manufacturer, Indian Electronic Component Supplier/Distributor, ISO Certified Company
PRODUCTS
  UPS  |  CVT  |  DC Power Supply  |  SMF Battery  |

UPS ES Series



  TE Series  |  T Series  |  Senior Series  |  ES Series  | WL Series  |

 TECHNICAL INFORMATION / SPECIFICATIONS (On-line Sinewave UPS)

UPS Models

ES1000

ES2000

ES3000

Capacity & Output
Current Rating

1KVA/700W
4 Amps

2KVA/1400W
8.7 Amps

3KVA/2100W
13.6 Amps

Battery Input,
Internal-7.2 AH Bank

36Vdc

96Vdc

96Vdc

Input Voltage

160-295 Vac for > 70% linear load, Input votage range will improve to <120V for <50% load

Input Frequency

45 - 55Hz

Input Power factor

Near Unity. >0.95

Charger, Internal

Float charger, CV/CC, 1.4A/SMPS, approx. 8 hours chare-up time to 90% capacity

Battery Type
Internal

SMF, with option to connect an external battery bank, with charger
for higher run-time requirements in the ESxxxxL series UPS

Backup Time, with
internal battery bank

5 min. at Full load &
12 min. at Half load

8 min. at Full load &
19 min. at Half load

5 min. at Full load &
16 min. at Half load

Output Voltage

220Vac ± 2%

Output Frequency,
battery mode

50Hz ± 2%

Freq. Synchronisation

Inverter output frequency is synchronized with the line input

Efficiency, AC-AC

83%

85%

85%

Waveform

Sinewave

 

 

Distortion at linear

<3% at full load and

 

 

and at non-linear load

<4%

<5%

<5%

Bypass Function,
Utility Mode to /
from battery Mode

The UPS uses the Input AC line as its stand-by source. in case of an O/L
condition, the UPS will automatically transfer to the bypass line, if healthy
input conditions exist, within 4 msec (2.5ms typ.) to ensure that the critical
load(s) continue to operate

Auto Restart

Yes

Cold/Black Start

Yes

Over Load,
Transfer to Bypass

> 110% of FL: 30 seconds delay,
150% of FL: 200 msec. delay

Protections

Input or Output UV/OV conditions. Inverter shutdown protection,
Short circuit on output. The UPS shuts down & won’t transfer to bypass
mode, will work normally once short circuit condition is removed

Crest factor

Better than 3

Ambient Conditions

0° to 50° C, Natural Convection Cooling

Audible Noise

< 50 dBA at 1 metre

Computer Interface

LAN/RS232 Interface: Mains Fail, Battery Low, Remote Shutdown

Cooling

Convection

Dimensions in mm
W x D x H

144 x412 x 213

191 x470 x 338

191 x470 x 338

Packed Weight,
with internal battery

15 Kg.

35 Kg.

36 Kg.

* Since upgradation is a continuous process, specs. are subject to change without notice.