UPS Models
|
ES1000
|
ES2000
|
ES3000
|
|
Capacity & Output
Current Rating
|
1KVA/700W
4 Amps
|
2KVA/1400W
8.7 Amps
|
3KVA/2100W
13.6 Amps
|
|
Battery Input,
Internal-7.2 AH Bank
|
36Vdc
|
96Vdc
|
96Vdc
|
|
Input Voltage
|
160-295 Vac for > 70% linear load, Input votage
range will improve to <120V for <50% load
|
|
Input Frequency
|
45 - 55Hz
|
|
Input Power factor
|
Near Unity. >0.95
|
|
Charger, Internal
|
Float charger, CV/CC, 1.4A/SMPS, approx. 8 hours
chare-up time to 90% capacity
|
|
Battery Type
Internal
|
SMF, with option to connect an external battery
bank, with charger
for higher run-time requirements in the ESxxxxL
series UPS
|
|
Backup Time, with
internal battery bank
|
5 min. at Full load &
12 min. at Half load
|
8 min. at Full load &
19 min. at Half load
|
5 min. at Full load &
16 min. at Half load
|
|
Output Voltage
|
220Vac ± 2%
|
|
Output Frequency,
battery mode
|
50Hz ± 2%
|
|
Freq. Synchronisation
|
Inverter output frequency is synchronized with
the line input
|
|
Efficiency, AC-AC
|
83%
|
85%
|
85%
|
|
Waveform
|
Sinewave
|
|
|
|
Distortion at linear
|
<3% at full load and
|
|
|
|
and at non-linear load
|
<4%
|
<5%
|
<5%
|
|
Bypass Function,
Utility Mode to /
from battery Mode
|
The UPS uses the Input AC line as its stand-by
source. in case of an O/L
condition, the UPS will automatically transfer
to the bypass line, if healthy
input conditions exist, within 4 msec (2.5ms typ.)
to ensure that the critical
load(s) continue to operate
|
|
Auto Restart
|
Yes
|
|
Cold/Black Start
|
Yes
|
|
Over Load,
Transfer to Bypass
|
> 110% of FL: 30 seconds delay,
150% of FL: 200 msec. delay
|
|
Protections
|
Input or Output UV/OV conditions. Inverter shutdown
protection,
Short circuit on output. The UPS shuts down &
wont transfer to bypass
mode, will work normally once short circuit condition
is removed
|
|
Crest factor
|
Better than 3
|
|
Ambient Conditions
|
0° to 50° C, Natural Convection Cooling
|
|
Audible Noise
|
< 50 dBA at 1 metre
|
|
Computer Interface
|
LAN/RS232 Interface: Mains Fail, Battery Low,
Remote Shutdown
|
|
Cooling
|
Convection
|
|
Dimensions in mm
W x D x H
|
144 x412 x 213
|
191 x470 x 338
|
191 x470 x 338
|
|
Packed Weight,
with internal battery
|
15 Kg.
|
35 Kg.
|
36 Kg.
|
|
* Since upgradation is a continuous process,